SPECIFICATIONS

Hardware Capacity
21U + 2U x 2
Heat Dissipation Capacity
80 kW
Dimensions (L x W x H)
Tank (0.91m x 1.16m x 1.49m)
CDU (0.86m x 0.48m x 1.62m)
Weight
Tank: 450 kg (w/o coolant); 1065kg (w/ coolant)
CDU: 325 kg
CDU Power Consumption
0.75 kW
Coolant Volume
750 L
Electrical Connection
PDU: IEC 60309 63A-3P+N+E, 6H, Plug x2
CDU: IEC 60320 C19, Plug x1
Footprint
2.1m x 0.9m
Server Depth Supported
900mm
Cooling Water Inlet
20-35°C
Water Flow Rate
240 LPM
PUE
1.02
Ordering Information
Tank: 9NA1P0EB0KR-00-2*
IT Lift: 25FT3-000000-T0R
IT Dry Rack: 25FT5-000000-U0R
Drain Oil Pump: 25FT4-000000-K0R
* The entire materials provided herein are for reference only. GIGABYTE reserves the right to modify or revise the content at anytime without prior notice.
* Advertised performance is based on maximum theoretical interface values from respective Chipset vendors or organization who defined the interface specification. Actual performance may vary by system configuration.
* All trademarks and logos are the properties of their respective holders.
* Due to standard PC architecture, a certain amount of memory is reserved for system usage and therefore the actual memory size is less than the stated amount.

RESOURCES

Back to A1P0-EB0